A switching cubicle containing a circuit-breaker that can electrically connect or separate the two busbar sections under appropriate operating conditions. In this lineup it is normally OPEN, so Busbar A and Busbar B are supplied independently. Its upper (busbar-side) primary contacts are connected to Busbar B; its lower primary contacts lead into the link compartment at the bottom of the cubicle.
A cubicle providing a physical busbar connection or transition path within the lineup. It does not contain a circuit-breaker. Here it takes Busbar A down from the busbar compartment to a bus link that passes through the side wall into the coupler cubicle. The riser is always at Busbar A potential.
The main busbar is physically interrupted at the section barrier between =H05 and =H06. A withdrawable breaker connects to only one busbar run through its upper contacts, so the other section has to be brought to the breaker's lower contacts. That is the riser's job. Together, the riser and the coupler form one switchable connection between the two sections.
With Source B feeding Busbar A, the same path is used in the opposite direction.
| Feature | Bus Coupler =H06 | Bus Riser =H05 |
|---|---|---|
| Circuit-breaker | Yes: VCB, 1250 A | No |
| Makes / breaks load and fault current | Yes | No: fixed connection |
| Protection relay | Yes: 50/51, switch-on-to-fault, transfer logic | No (may house bus VT / metering) |
| Normal state | OPEN | Permanently connected to Busbar A |
| Interlocks | 2-out-of-3, 86 lockout, dead-bus check, racking | Compartment access only |
| Carries current | Only when closed | Only when the coupler is closed |